Weight | 0.16 g |
---|---|
Dimensions | 100 × 17.5 × 110 mm |
Description |
2 CH Analogue input Modbus RTU – Modbus TCP-IP module |
Power Supply |
19.. 28 Vac (50..60 Hz), 11.. 40Vdc |
Isolation |
1500 Vac |
Analog Inputs |
2-CH 0-20 mA / 0-30 V; 16 bit ADC resolution |
Accuracy |
0,1% |
Interfaces |
1 Ethernet 10/100 Mbps port, N°2 RS485 ports, N°1 mini USB 2.0 port |
Protocols |
ModBUS RTU, ModBUS TCP-IP, http |
Setup |
Software (EASY SETUP), DIP switch (address, baud rate), web server (remote I/O configuration) |
ZE-2AI
2 CH Analogue input Modbus RTU – Modbus TCP-IP module
ZE-2AI is a I/O module with 2 analog inputs, slave for Modbus TCP-IP communication (Ethernet) and Modbus RTU. The module insures server mode for the Ethernet communication port with ModbusTCP-IP protocol: Ethernet port (10-100 Mbps), 4 client, Embedded Webserver. ZE-2AI allows the possibility to set the parameters via internet (Web-server) or USB (Easy setup software) and also Modbus registers repetition on TCP-IP protocol (1 Ethernet port) and Modbus RTU (2 independent RS485 slave serial ports). Baud rate for ModbusRTU starts from 1.200 up to 115.200 baud. Analog inputs can be setted in voltage or current scales.
Additional information
Related products
Z-8TC-1
CH-8 thermocouple input module / RS485
The Z-8TC-1 is an interface for Thermocouple sensors (J, K, E, N, S, R ,B ,T) and generic sensor with mV as standard output signal. The number of input is 8 and each input is independent from each other. It's a ModBUS Slave and can be coupled with any ModBUS Master device. A 6-way galvanic isolation among Power supply // input // RS485 circuits assures the integrity of your data (each couple of channels is isolated from the other circuits).
Z-4RTD2
4-CH RTD input module / RS485
Z-4RTD2 is a converter for platinum or nickel RTD sensors (PT100, PT1000, PT500, Ni100 with 2,3 or 4 wires) with four independent and isolated measuring channels. The module is characterized by a 6-way isolation up to 1.5 kV (Power supply // Single input channel (x4) // RS485 serial communication). Power supply and serial bus wiring via the Z-PC-DINAL2-17.5 accessory (or Z-PC-DIN2-17.5 for existing BUS extensions) ensures a quick and easy DIN rail setup. Through the microUSB port on the front panel it is possible to configure the device via PC software EASY Setup. The configuration parameters can also be set via DIP-switch.
Z-SG
Z-8AI
8-CH analog input module / RS485
The Z-8AI is used to interface analog inputs (Voltage or current, also with bipolar range) with Modbus system. The modules is able to supply all 8 current loops at the sameb time, this is very useful for 2-wire sensors because the wiring does not need an external power supply. It’s a ModBUS Slave and can be coupled with any ModBUS Master device. A 3-way galvanic isolation among Power supply // input // RS485 circuits assures the integrity of your data.
Z-4TC
4-CH thermocouple input module / RS485
Z-4TC is an interface for Thermocouple sensors (J, K, E, N, S, R, B ,T) and generic sensor with mV as standard output signal. The number of input is 4 and each input is independent from each other. It’s a ModBUS Slave and can be coupled with any ModBUS Master device. A 3-way galvanic isolation among Power supply // input // RS485 circuits assures the integrity of your data.
Z-8NTC
Z-DAQ-PID
Universal I/O module with PID Control
Z-DAQ-PID has a universal analog input (mA, V, PT100, TC, Ohm) and an active output 4..20 mA or 0..20 mA for continuos or PWM (pulse-width modulation) loop control. This functionality can be disabled and the unit can be used as analog input and analog output indipendent from each other. The module is ModBUS Slave and can be coupled with any ModBUS Master device. A 3-way galvanic isolation among Power supply // input // RS485 circuits assures the integrity of your data.
Z-8TC-LAB
CH-8 thermocouple input module / RS485 with two-way pull-out terminals
The Z-8TC-LAB is a digital thermocouple converter, with eight measurement channels, isolated from the power supply and serial communication line up to 1.5 kVac. The same isolation is provided between channels belonging to different groups of terminals: the module has total isolation of six points.